Building OL = 360; threshold = 30. Sprinklered = yes → required rating 0 hr.
Corridors shall have a fire-resistance rating in accordance with Table 1020.2. Corridor walls are permitted to be unrated where the occupant load served is 30 or fewer, or where the building is protected throughout by an automatic sprinkler system per the conditions in the table.