Fire & Life Safety Code Analysis
1420 SE Division St, Portland, OR · Portland, OR
This analysis evaluates the referenced construction documents against the adopted IBC 2021 and local amendments in effect for Portland, OR. Findings are derived from automated extraction of the plan set and verified against the applicable code sections cited below.
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. Where occupants from accessory areas egress through a primary space, the accessory occupant load shall be added.
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. Where occupants from accessory areas egress through a primary space, the accessory occupant load shall be added.
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. Where occupants from accessory areas egress through a primary space, the accessory occupant load shall be added.
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. Where occupants from accessory areas egress through a primary space, the accessory occupant load shall be added.
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. Where occupants from accessory areas egress through a primary space, the accessory occupant load shall be added.
The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.5. Where occupants from accessory areas egress through a primary space, the accessory occupant load shall be added.
1005.3.1 Stairways. The capacity, in inches, of means of egress stairways shall be calculated by multiplying the occupant load served by 0.3 inch per occupant, or 0.2 inch where the building is equipped throughout with an automatic sprinkler system and an emergency voice/alarm communication system. 1005.3.2 Other egress components. The capacity shall be calculated by multiplying the occupant load by 0.2 inch, or 0.15 inch under the same sprinkler/alarm conditions.
1005.3.1 Stairways. The capacity, in inches, of means of egress stairways shall be calculated by multiplying the occupant load served by 0.3 inch per occupant, or 0.2 inch where the building is equipped throughout with an automatic sprinkler system and an emergency voice/alarm communication system. 1005.3.2 Other egress components. The capacity shall be calculated by multiplying the occupant load by 0.2 inch, or 0.15 inch under the same sprinkler/alarm conditions.
1005.3.1 Stairways. The capacity, in inches, of means of egress stairways shall be calculated by multiplying the occupant load served by 0.3 inch per occupant, or 0.2 inch where the building is equipped throughout with an automatic sprinkler system and an emergency voice/alarm communication system. 1005.3.2 Other egress components. The capacity shall be calculated by multiplying the occupant load by 0.2 inch, or 0.15 inch under the same sprinkler/alarm conditions.
Two exits or exit access doorways from any space shall be provided where the occupant load or the common path of egress travel distance exceeds the values in Table 1006.2.1.
Two exits or exit access doorways from any space shall be provided where the occupant load or the common path of egress travel distance exceeds the values in Table 1006.2.1.
Two exits or exit access doorways from any space shall be provided where the occupant load or the common path of egress travel distance exceeds the values in Table 1006.2.1.
The exit access travel distance shall not exceed the values given in Table 1017.2, measured from the most remote point within a story to the entrance of an exit along the natural and unobstructed path of egress travel.
The exit access travel distance shall not exceed the values given in Table 1017.2, measured from the most remote point within a story to the entrance of an exit along the natural and unobstructed path of egress travel.
Two exits or exit access doorways from any space shall be provided where the occupant load or the common path of egress travel distance exceeds the values in Table 1006.2.1.
Corridors shall have a fire-resistance rating in accordance with Table 1020.2. Corridor walls are permitted to be unrated where the occupant load served is 30 or fewer, or where the building is protected throughout by an automatic sprinkler system per the conditions in the table.
The height of buildings, in feet, shall not exceed the limits specified in Table 504.3 based on the type of construction and occupancy classification.
The height of buildings, in feet, shall not exceed the limits specified in Table 504.3 based on the type of construction and occupancy classification.
The height of buildings, in feet, shall not exceed the limits specified in Table 504.3 based on the type of construction and occupancy classification.
Occupancies in a mixed-occupancy building shall be separated in accordance with Table 508.4, unless designed as nonseparated occupancies under Section 508.3.
Occupancies in a mixed-occupancy building shall be separated in accordance with Table 508.4, unless designed as nonseparated occupancies under Section 508.3.
Occupancies in a mixed-occupancy building shall be separated in accordance with Table 508.4, unless designed as nonseparated occupancies under Section 508.3.
Building elements shall have a fire-resistance rating not less than that specified in Table 601 based on the type of construction.
Prep Area (Room 106) use classification
Room tagged "PREP" with tables shown. Classify as Assembly (A-2) accessory to dining, or as Business/food prep support?
Default applied: Assembly, unconcentrated — 15 net (conservative)
Drives occupant load and whether the space is added to the A-2 aggregate for exit count and separation.
Door 108 clear width
Side exit clear width could not be confirmed from the schedule (low-confidence extraction). Confirm 34" clear.
Default applied: 34" clear width (from partial schedule read)
Determines egress capacity available at this exit and whether it counts toward required exits.
A-2 / S-1 occupancy separation
Dry Storage (S-1) abuts Kitchen (A-2). Confirm whether occupancies are designed as separated or non-separated (508.3 vs 508.4).
Default applied: Separated occupancies — 1 hr assumed at demising wall
Non-separated triggers the most restrictive height/area; separated requires the rated wall to be shown.