Capitol Hill Office Fit-Out

Seattle, WA · IBC 2021

Findings

Height & Area
1
Fire Resistance
1
Occupant Load
6
Egress Capacity
3
Exit Count
1
Common Path
1
Travel Distance
2
Corridor Rating
1
Dining RoomA-2 · 2760 sfBar / StandingA-2 · 640 sfPrep AreaA-2 · 520 sfKitchenA-2 · 1360 sfDry StorageS-1 · 560 sfManager OfficeB · 480 sf1841283572472"36"34"168 ft262 ft64 ft
EVIDENCE · Sheet LS1.1 · IBC 1006.2.1 · region [630,300]
7 ft
1/8" = 1'-0"
overlays live
A-2 assemblyB businessM mercantileS-1 storageegress pathoccupant load
13 / 16

Manager Office — common path of egress travel

IBC 1006.2.1IBC 2021
Pass
Measured64 ft measured · 100 ft limit
RequirementCommon path of egress travel must not exceed the tabulated limit before two paths are available.
Derivation

Measured common path = 64 ft. Group B limit = 100 ft.

Adopted code text
Two exits or exit access doorways from any space shall be provided where the occupant load or the common path of egress travel distance exceeds the values in Table 1006.2.1.
Sheet LS1.1Medium confidence · 85%