Findings
16
across 9 sections
Pass
13
compliant findings
Deficiencies
1
require correction
Needs input
5
flags + design questions
Trust & coverage
asserted findings correct on golden set
vs. an experienced reviewer
Precision and recall are tracked separately. Partial recall with full precision is acceptable and labeled; an incorrect citation is a P0 defect.
Findings by report section
| Section | Pass | Fail | Input | Recall |
|---|---|---|---|---|
| Height & Area | 1 | — | — | 100% |
| Fire Resistancemanual review | 1 | — | — | 70% |
| Occupant Load | 5 | — | 1 | 100% |
| Egress Capacity | 2 | — | 1 | 100% |
| Exit Count | 1 | — | — | 100% |
| Common Path | 1 | — | — | 100% |
| Travel Distance | 1 | 1 | — | 100% |
| Corridor Rating | 1 | — | — | 100% |
1 section below recall threshold. Rendered as "manual review required" rather than silently thin — a human must produce these findings.
Questions for the design team — 3
Prep Area (Room 106) use classification
IBC Table 1004.5Room tagged "PREP" with tables shown. Classify as Assembly (A-2) accessory to dining, or as Business/food prep support?
DEFAULT · Assembly, unconcentrated — 15 net (conservative)
Drives occupant load and whether the space is added to the A-2 aggregate for exit count and separation.
Door 108 clear width
IBC 1005.3Side exit clear width could not be confirmed from the schedule (low-confidence extraction). Confirm 34" clear.
DEFAULT · 34" clear width (from partial schedule read)
Determines egress capacity available at this exit and whether it counts toward required exits.
A-2 / S-1 occupancy separation
IBC Table 508.4Dry Storage (S-1) abuts Kitchen (A-2). Confirm whether occupancies are designed as separated or non-separated (508.3 vs 508.4).
DEFAULT · Separated occupancies — 1 hr assumed at demising wall
Non-separated triggers the most restrictive height/area; separated requires the rated wall to be shown.
Draft generated Jul 12, 9:14 AM · for licensed human review · liability remains with the stamping firm.